Instrument air systems may be duplex compressors Instrument Air is air primarily for running tools as a substitute for Nitrogen. Teflon or the like are no longer permitted on cylinder oxygen manifolds.

NFPA 99 Standard for Health Care Facilities 1999 Edition

Medical Air in was not permitted to be used for any non-patient purpose. Instrument air systems may be duplex compressors. Labelling is critical in these cases, because its not the usual thing to have these manifold parts separated. Dont look for any Appendix - theyre renamed Annexes.

NFPA Editions

The owner must take pains to ensure their verifier is competent in gas analysis. However, these dryers have a fundamental limitation in the fact that they are subject to re entrainment of the water and thus to a bathtub shaped performance curve see the figure below. Wondering how to keep informed about changes in the rapidly evolving medical gas industry? The best known was the requirement for Lab vacuum, when connected to a medical-surgical vacuum source, to be run through a separator upstream of the receiver.

In those two systems, if the allowance for performing the tests in system gas is also used, this test becomes absolutely pointless. This configuration will be the least expensive installation, but duplexed compressors are also acceptable. Cylinders have always had to be secured. In light of the changes in the requirements. This will have its most dramatic effect on dentists, who have acquired some notoriety for being indifferent to the systems they install and the way those systems are installed.

Installing one will inevitably reduce the overall resistance of the medical gas systems to fire, and thus they have been resisted. Otherwise, specific tests are required which are a limited subset of the larger testing regime. Regrettably, this is likely to be an oft ignored requirement, because these monitors are usually ignored now, and these requirements are in a section of the standard few people ever read. This effects installation, the qualifications for installers, testing and the qualifications for verifiers among other effects. The idea is to prevent a domino effect when changing or manipulating cylinders.

This seemingly subtle change is huge in its potential consequences. It is required only on these gases because their vapor pressure is low and at temperatures below this, they may not have the pressure to properly operate their respective manifolds. It used to be rare to see the condition which would invoke this new requirement. Distribution of the Electronic version is permitted only where the whole is transmitted without alteration, including this notice.

Regrettably, developments in health care simply confetti any neat formula, and thus we fall back on the next best thing - a set of rules. Making the dew point absolute makes the test much easier to perform but reduces its sensitivity. Many engineers prefer refrigerant dryers because of their low cost and because they are used to them. There are issues with this qualification, the greatest being that as of this writing, no one issues such a qualification. In effect, the standard now requires the use of dryers without a bathtub shaped performance curve and insists they be operated totally in accordance with manufacturers specification.

In addition, there are some obvious other concerns, like discharging oxidizing gases near ignition sources. The standard does not state which branch equipment, life safety or critical. The change and reference is in the left column, and our reflections on the possible consequences and implementation of the change in the right column.

NFPA - NFPA Standard for Health Care Facilities EditionNFPA Editions

They are required for all sources for the first time in this edition. In the edition, the rules were obscure and scattered, which made even starting the decision process difficult. They are all moved to the Annex, reflecting the fact the Figures have never been and are not in this edition, types of exception handling in java pdf mandatory or enforceable. The use of these fittings has been vigorously debated over several cycles. The intent is to ensure the monitors are operational as many now are not.

Under normal operation, only one dryer. Without a doubt, the chapter had become more cumbersome and harder and harder to understand with each revision cycle.

The change reflects a valid need, but in practice particularly given the specialized knowledge required of the verifier could result in testing being performed in ways which are not valid. In addition, this provision helps define how to install a local reserve for areas with very high criticality. Aftercoolers, where required, shall be duplexed and provided with individual condensate traps. Find the discussion of whats new here. The decision tree is summarized overleaf.

Continuing Education Publication

NFPA - NFPA Standard for Health Care Facilities Edition

Air manifolds are obviously not toxic by definition and dont increase the oxygen in the room, so they are exempted. The standard does not state how big these openings must be. BeaconMeds also makes available a specific guide for medcal gases in small facilities. Under the version a medical air compressor system was required in the text to not add contaminants in the form of particulate matter, odor or other gases.

It applies for instance to a bulk system enclosed in a solid enclosure such as a brick or block wall. The practical effects of this change are likely to be small. Since they are now arranged one paragraph, one requirement, there is less of the three paragraphs and a figure that bear problem which plagued earlier versions.

The Annex therefore now contains most of the Tables and all of the Figures. Any material in the high pressure oxygen stream must be regarded as potential fuel, and it is wise to avoid any such materials if possible. Please refer to the actual standard prior to any real decision. The practical effect for the typical facility is likely to be small. No reference - deleted requirement Relief valves no longer have to close automatically.

However, with security generally becoming a big issue, these kind of enclosures are sure to become more common. The committee was exceedingly fortunate in their Chair.

That means that even an enforcer who is not especially expert in medical gas should generally be able to read and understand the requirements. The exception is medical and instrument air. The definitions no longer contain enforcement criteria as such - an innocuous sounding change with. This excluded use by staff for applications like decontamination, isolation rooms etc.

Related Products

Nothing in an Annex is enforceable. Dont look for a separate vacuum section. In practice, since the test is there to detect wet pipe, either test properly performed is likely to acheive the desired result.

Aftercoolers, where required, shall be provided with individual condensate traps. It allows a reserve header to be located separately from the rest of the manifold.

Continuing Education Publication

Buy NFPA 70 National Electrical Code (NEC) Softbound

The figures were out of sync with the text and antediluvian in presentation. The ability of a verifier to accurately measure to the lower limit and the relevance of that lower limit were debated and it was determined to increase the accumulation which represented failure. Relief valves often weep after operation, never completely reseating. There is nothing in the body of the chapter which is not enforceable. The most important changes are listed on the following pages in two column format.